dc.description.abstractSistemas de água de resfriamento, assim como as demais utilidades, em geral sofrem um tratamento secundário em escalas de priorização. No entanto em muitos casos problemas associados a estas são prejudiciais à eficiência e até a continuidade dos processos industriais. Neste contexto encontrasse a corrosão sob depósito em permutadores de calor que operam com água de resfriamento. O presente estudo fez a comparação e análise dos parâmetros de projeto e dados de operação de dois grupos de permutadores, relativos a duas torres de resfriamento distintas: Um de uma unidade de lubrificantes, composto de quatro permutadores trabalhando independentes entre si; e um do FCC, composto de oito permutadores trabalhando dois a dois em série, em quatro pares. Desta análise foi concluída a importância da monitoração contínua de variáveis operacionais como vazão, temperaturas de entrada e saída, tanto das cargas quanto da água de resfriamento, sendo esta última a mais crítica. Não somente a corrosão sob depósito, mas também os demais processos associados à deposição e à corrosão são termicamente ativados, fazendo do controle das temperaturas um dos aspectos mais importantes.pt_BR
dc.description.abstractWater cooling systems, as other utilities in general have a secondary treatment in scales of work and analyses prioritization, however in many cases these problems are detrimental to efficiency and even the continuity of industrial processes. In this context we found under deposit corrosion of heat exchangers operating in cooling water systems. This study was a comparison and analysis of design parameters and operating data from two groups of heat exchangers, each on from two different cooling towers: a unit of a lubricant, composed of four heat exchangers working independent of each other, and one of the plant’s FCC, where eight heat exchanger still working in four couples. From this analysis was concluded the importance of continuous monitoring of operational variables such as flow, temperature of inlet and outlet of both the loads on the cooling water, with the latter being the most critical. Temperature control is important not only for under deposit corrosion, but also for other processes associated with deposition and others corrosion processes, since they are thermal activated.en
dc.format.mimetypeapplication/pdf
dc.language.isoporpt_BR
dc.rightsOpen Accessen
dc.subjectTrocador de calorpt_BR
dc.subjectCorrosãopt_BR
dc.titleMecanismo de deterioração, devido a corrosão sob depósito, em feixes de permutadores do sistema de água de resfriamentopt_BR
dc.typeDissertaçãopt_BR
dc.identifier.nrb000737018pt_BR
dc.degree.grantorUniversidade Federal do Rio Grande do Sulpt_BR
dc.degree.departmentEscola de Engenhariapt_BR
dc.degree.programPrograma de Pós-Graduação em Engenharia Minas, Metalúrgica e de Materiaispt_BR
dc.degree.localPorto Alegre, BR-RSpt_BR
dc.degree.date2009pt_BR
dc.degree.levelmestrado profissionalpt_BR


Thumbnail
   

Este item está licenciado na Creative Commons License

Mostrar registro simples