Show simple item record

dc.contributor.authorCosta, Lucas Araujo dapt_BR
dc.contributor.authorGazzana, Daniel da Silvapt_BR
dc.contributor.authorLeborgne, Roberto Chouhypt_BR
dc.date.accessioned2020-12-15T04:10:01Zpt_BR
dc.date.issued2020pt_BR
dc.identifier.issn1532-5016pt_BR
dc.identifier.urihttp://hdl.handle.net/10183/216519pt_BR
dc.description.abstractSince voltage interruptions, sags and swells are Power Quality (PQ) disturbances with great economic impact, studies that seek alternatives to mitigate its effects have been conducted extensively. The PQ Brazilian standard names these disturbances as Short-Duration Voltage Variations (SDVVs), classified them in terms of magnitude, duration, and frequency of occurrence. These parameters are used to calculate the Impact Factor (IF) of SDVVs, a severity-characterization index of their incidence. In this context, this work assesses the influence of three-phase transformer winding connection and neutral grounding on the quantities of SDVVs and the IF observed by an industrial consumer in a distribution system. Fault simulations at ATPEMTP perform the study, considering two different winding connections for the secondary transformer and applying a grounding resistance to the neutral of the main transformer of the distribution system. The SDVVs are verified in two different ways: phase-to-ground and phase-to-phase voltages. It is observed that there are differences in these quantities and for the value of the IF due to the winding connection of the secondary transformer, the value of the neutral grounding resistance of the main transformer and the ways of voltage verification.en
dc.format.mimetypeapplication/pdfpt_BR
dc.language.isoengpt_BR
dc.relation.ispartofElectric Power Components and Systems [recurso eletrônico]. [London] : Taylor & Francis, 2020. Vol. 48, no. 8 (2020), p. 858-869pt_BR
dc.rightsOpen Accessen
dc.subjectNeutral groundingen
dc.subjectTransformadorespt_BR
dc.subjectTensão elétricapt_BR
dc.subjectTransformer winding connectionen
dc.subjectShort-duration voltage variationen
dc.subjectAterramento elétricopt_BR
dc.subjectEnergia elétrica : Distribuiçãopt_BR
dc.subjectPower qualityen
dc.subjectLoad connectionen
dc.subjectDistribution systemen
dc.titleInvestigation of main and secondary transformers on mitigation of voltage sags, swells and interruptions in unbalanced medium voltage distribution systemspt_BR
dc.typeArtigo de periódicopt_BR
dc.identifier.nrb001119185pt_BR
dc.type.originEstrangeiropt_BR


Files in this item

Thumbnail
   

This item is licensed under a Creative Commons License

Show simple item record